Overview

CISA published ICSA-26-281-02 on 8 October 2026 for Grid Protection Alliance (GPA) openPDC and openHistorian. CISA’s record names the products but does not describe them. As general background (not from CISA), openPDC is an open-source phasor data concentrator that collects synchrophasor streams from PMUs and forwards them to control rooms and analytics, and openHistorian is the companion time-series archive. CISA lists the Energy sector, worldwide deployment, and a US-headquartered vendor.

The advisory carries six CVEs. Two are rated 9.8 on CVSS v3.1. We review them here because the Docker image has no fix, and because one fix does not reach upgraded installations by default.

The six vulnerabilities

Scores below are CVSS v3.1 base scores published by CISA (ics-cert@hq.dhs.gov). NVD lists the CISA scores as “Secondary” and showed all six CVEs as “Awaiting Analysis” when we checked on 5 November 2026.

CVECWEComponentCVSS v3.1
CVE-2026-100730CWE-502 Deserialization of Untrusted DataService console (openPDC, openHistorian)9.8
CVE-2026-105278CWE-798 Hard-coded CredentialsopenPDC Docker image9.8
CVE-2026-104629CWE-470 Unsafe ReflectionAdapter loading (openPDC, openHistorian)8.8
CVE-2026-105281CWE-306 Missing AuthenticationInternal data publisher (openPDC)7.5
CVE-2026-85479CWE-306 Missing AuthenticationSTTP data publisher (openPDC)5.3
CVE-2026-101022CWE-918 SSRFModbus connection feature (openPDC)4.3

Technical detail

CVE-2026-100730. The service console deserializes a client-supplied data structure, which lets an attacker trigger deserialization of an arbitrary object graph and run code as the service account. With Windows Authentication enabled, the attacker must already be authenticated. On systems without it, the console is reachable by an unauthenticated network attacker. GPA’s notice (ID=4056) names BinaryFormatter and the default console port 8500, and says Windows Authentication is disabled on Linux; these details are from the GPA notice only and are not reproduced in CISA’s advisory, and we could not independently open that notice. If the Linux statement holds, Linux deployments would sit in the worse case. That inference is ours.

CVE-2026-105278. The published openPDC Docker image ships a fixed administrative credential with no forced change on first use. Anyone who can reach the management interface can authenticate as administrator.

CVE-2026-104629. The component loader constructs any specified type without verifying adapter authenticity or integrity. It needs an authenticated account plus the ability to write a file to the host, then runs constructor code as the service account. The 8.8 is CISA’s score (AV:N/PR:L); exploitation needs both an account and the ability to write a file to the host. GPA’s notice (ID=4054) rates it Low; that rating is from the GPA notice only.

CVE-2026-105281 and CVE-2026-85479. In default configuration, the internal data publisher and the STTP publisher accept unauthenticated connections. The first lets a client retrieve the full device and measurement topology, which is useful reconnaissance for anyone targeting a PMU network.

CVE-2026-101022. The Modbus feature accepts a caller-chosen destination address and port, so an authenticated user can probe internal hosts.

Affected and fixed versions

ProductFixApplies to
openPDC2.9.477 or laterCVE-2026-104629 (affected: below 2.9.477)
openPDC2.9.482 or laterCVE-2026-100730, 105281, 85479 (affected: below 2.9.482)
openHistorian2.8.580 or laterCVE-2026-104629 (affected: below 2.8.580)
openHistorian2.8.585 or laterCVE-2026-100730 (affected: below 2.8.585)
openPDC Docker imageNoneAll of the above. GPA does not recommend the image for production and has not published fixes to it

Note: CISA’s CSAF product tree also marks openHistorian below 2.8.585 as known affected by CVE-2026-105281, 85479 and 101022, although the advisory text describes those flaws on openPDC. We follow CISA’s descriptions in the tables and flag the mismatch; check both products.

Two details from CISA’s remediation entries matter in the field:

  • The fix for CVE-2026-105281 and CVE-2026-85479 (2.9.482 is inferred from the affected-version ranges in CISA’s product tree; the remediation text names no version) changes the default to bind the publishers to loopback, but only for new installations. Upgraded installations keep their old binding. Operators must check the setting by hand.
  • CVE-2026-101022 has no code fix and no fixed version in CISA’s record, only a mitigation. GPA recommends firewalling Modbus and blocking loopback and RFC 1918 destinations unless required.

Exploitation status

CISA’s embedded SSVC data (dated 5 October 2026) records exploitation as “None” for all six and automatable “Yes” for CVE-2026-100730, 105278, 105281 and 85479. CISA states that no known public exploitation specifically targeting these vulnerabilities has been reported to it. None of the six CVEs appears in the CISA KEV catalog (version 2026.11.04, searched 5 November 2026). Our assessment: the unauthenticated console and the default Docker credential are low-effort bugs, so internet-exposed instances should be treated as urgent regardless.

Operational impact

Phasor data concentrators sit at a sensitive point: they aggregate wide-area measurements used for situational awareness and, in some utilities, protection and control analytics. Our assessment is that code execution on a PDC primarily threatens data integrity and availability of the measurement stream and gives a foothold for lateral movement, rather than direct breaker operation, though this depends on how each utility consumes PDC output. We have no deployment data for either product.

What to do

  1. Inventory every openPDC, openHistorian and Docker-based instance, including research and test systems that may be connected to production PMU feeds.
  2. Upgrade to openPDC 2.9.482 and openHistorian 2.8.585 or later.
  3. Firewall port 8500 to local or named management hosts, and enable Windows Authentication where supported.
  4. Check the binding of the internal and STTP publishers on upgraded hosts and restrict them to loopback or trusted hosts.
  5. Replace Docker deployments in production; GPA does not recommend the image for production use. If one must stay, keep it off any routable network. Changing the credential is our suggestion only, since neither CISA nor GPA documents a way to do it.
  6. Restrict write access to application folders and run the services with least privilege.
  7. Place the PDC at a defined zone boundary (Purdue levels 3 to 3.5 in most utility designs, our assessment) with only PMU and consumer flows permitted.

CISA credits Shubham Raj of Causal Security with reporting the vulnerabilities.